The RE-102R and RE-104R are 2-zone and 4-zone conventional fire alarm control panels designed for reliable fire detection in small to medium-sized commercial and industrial environments. These panels support conventional input devices and provide stable, easy-to-manage fire monitoring. Equipped with Notification Appliance Circuits (NAC), programmable Form-C relays, and RS-485 communication for remote annunciators, the system offers flexibility for site-specific requirements. Field programmable via an intuitive keypad, the panels continuously monitor wiring, AC supply, and battery status, ensuring dependable operation. Optional Ethernet and GSM connectivity enhance remote event reporting and system responsiveness.
| Zones | 2 or 4 (RE-102R / RE-104R) |
|---|---|
| Standby Current | 40 mA (2 Zone) / 50 mA (4 Zone) |
| Charging Voltage | 28 V ± 5% |
| Charging Current | 350 mA (Max) |
| Aux Output Voltage | 24 VDC (Regulated) |
| Aux Output Current | 100 mA (Max) |
| NAC Wiring Style | Class B |
| NAC Quantity | 1 |
| NAC Operating Voltage | 24 VDC (Regulated) |
| NAC Current | 350 mA |
| NAC EOL Resistor | 4K7, ½ Watt |
| Relay Type | Form C |
| Relay Quantity | 2 (Programmable) |
| Relay Contact Rating | 1A @ 30 VDC |
| Initiating Device Circuits | Class B |
| Normal Operating Voltage | 14 – 21 VDC |
| Alarm Current | 15 – 35 mA |
| Short Circuit Current | 42 mA (Max) |
| Loop Resistance | 50 Ω (Max) |
| EOL Resistor | 4K7, ½ Watt |
| Detector Standby Current | 6.8 mA (2.4 mA for detectors) |
| RS-485 Nodes | 1 |
| RS-485 Wiring | Class B, Twisted Pair |
| RS-485 Circuit Length | 1.2 km (Max) |
| RS-485 Loop Resistance | 100 Ω |