The RE-2554 is a microprocessor-based, UL-listed 4-zone conventional fire alarm control panel designed to deliver reliable fire detection for a wide range of applications. It features a 16 × 2 LCD display for clear system status and alarm information, with four independent detection zones for accurate area identification. Includes three common potential-free relay contacts and two common Notification Appliance Circuit (NAC) sounder outputs, ensuring effective alarm signaling and system integration. An inbuilt RS-485 communication port allows seamless connectivity with repeaters for extended monitoring. Operates on a switch-mode power supply (SMPS) with battery polarity protection and deep discharge protection for safe and stable performance. Suitable for schools, hospitals, hotels, banks, commercial buildings, and small to medium-scale industrial facilities.
| Primary Power | 120 – 220VAC ± 10%, 50 Hz, 2.5 Amps |
|---|---|
| Standby Power | 24V D.C (2 Nos of 12V, 12Ah Sealed Lead acid battery), Quiescent current: 120mA |
| Initiating Device Circuits | All zones Class B Style B/C (Programmable), Normal Voltage: 14–21 VDC, Alarm Current: 15–30mA, Short Circuit: 45mA max, Loop resistance: 100Ω max, End-Of-Line Resistor: 3.9KΩ, Standby Current: 7mA (2mA for Detectors) |
| Operating Condition | Temperature: 0–49°C / 32–120°F, Humidity: 93 ± 2% RH (non-condensing) |
| Charging Circuit | Charging Voltage: 28.2V ±0.5V, Max Current: 800mA |
| Notification Appliance Circuits | Class B Style Y wiring, Nominal Voltage: 24VDC, Current: 1.2A max (0.6A per circuit), Line Drop: 1.8V, End-Of-Line Resistor: 3.9KΩ |
| D.C. Output | Supervised 24VDC regulated, 300mA Max |
| Common Relays | Type: Form C, No of Relays: 3, Rating: 2A @ 30VDC, 0.5A @125VAC, Power Factor: 1.0 |